Back Button 2865751 Datasheet HTML 35Page - PHOENIX CONTACT 2865751 Datasheet HTML 36Page - PHOENIX CONTACT 2865751 Datasheet HTML 37Page - PHOENIX CONTACT 2865751 Datasheet HTML 38Page - PHOENIX CONTACT 2865751 Datasheet HTML 39Page - PHOENIX CONTACT 2865751 Datasheet HTML 40Page - PHOENIX CONTACT 2865751 Datasheet HTML 41Page - PHOENIX CONTACT 2865751 Datasheet HTML 42Page - PHOENIX CONTACT 2865751 Datasheet HTML 43Page - PHOENIX CONTACT Next Button
Zoom Inzoom in Zoom Outzoom out
 39 / 44 page
background image
Appendix - Safety-related applications (SIL 2)
en Version 05
PHOENIX CONTACT
A-2
Evaluation
Failures which are detected in the measuring transducer
and to which the transducer responds by switching to the
safe state are safe failures (λs).
Failures where the measuring transducer does not follow a
change of input signal or generates an output signal that de-
viates from the intended value by more than ±5%, are eval-
uated as dangerous failures (λd).
Both safe (λs) and dangerous (λd) failures can be detected
by diagnostic measures. Detected dangerous failures (λdd)
are handled in the same way as safe failures.
The monitoring functions refer to events whose cause is
detected and reported outside of the device.
Summary:
Together with the actual signal transmission, continuous
checks and diagnostic functions are performed in the mea-
suring transducers in order to detect faulty behavior.
The internal failure monitoring time (diagnostics test in-
terval) is the time taken to carry out and repeat these tests in
full. Random hardware faults are detected during this time.
The internal failure monitoring time is 50 seconds.
A1.2
Safety integrity requirements
A1.2.1 Failure rates: MACX MCR(-EX)-T-UIREL-UP
(-SP)(-C)
–
Type B device (according to EN 61508-2)
–
Safety Integrity Level (SIL) 2
–HFT = 0
–
1oo1d architecture
The total failure rate is: 1.34 * 10
-6
The MTBF (Mean Time Between Failures) is therefore
85 years.
The probability of a dangerous failure per hour for “continu-
ous demand” mode and the average probability of failure of
the specified function for “low demand” mode are deter-
mined from the error rate:
PFD
avg values
PFH* = 4.3 * 10
-8
/h
The calculation is performed assuming a checking interval
(T
PROOF) of 1 year and a repair time (MTTR) of 24 hours, a
test coverage (CPT) of 95% and a life time (LT) of 10 years.
On the basis of the value determined for the average proba-
bility of failure PFD
avg, the checking interval can be in-
creased to up to 5 years.
The values are valid under the following conditions:
–
The failure rates of the components used remain con-
stant throughout the period of use.
–
The propagation of failures by the device in the system
is not taken into consideration.
–
The repair time (replacement) is 24 hours.
–
The failure rates of the external power supply unit are
not taken into consideration.
–
The average temperature at which the device is to be
used is 40°C. In this case, normal industrial conditions
are assumed.
–
The specified failure rates are based on an average am-
bient temperature of 40°C. For an average ambient
temperature of 60°C, the failure rates must be multiplied
by factor 2.5. Factor 2.5 is based on guide values.
Safety/monitor-
ing function
Output sig-
nal range
Safe
state
Reason
Safety function
4 ... 20 mA
< 3.6 mA;
or
> 21 mA
Relay is
not con-
trolled
Deviation
> 5%
Input
monitoring
4 ... 20 mA
2 - 3.6
mA; >
21 mA
Line fault input
Output monitoring 4 ... 20 mA
= 0 mA
Line fault out-
put
As a result of the multiple connection options,
only two device types are considered in the con-
figurations for “RTD 3-wire” or “mV” in the follow-
ing. They represent all configurations with a
variable resistance at the input terminals or volt-
age or thermocouple inputs and always indicate
the most conservative case. The two device types
are:
1. MACX MCR(-EX)-T-UI-UP(-SP)(-C)
2. MACX MCR(-EX)-T-UIREL-UP(-SP)(-C)
FIT (Failure In Time)
1 FIT is 1 failure in 10
9
hours
Input:
RTD 3-wire connection method
Output:
Switching output 2 and 3 (redundant)
λ
SD
λ
SU
λ
DD
λ
DU
SFF
DC
D
0
2.34 *
10
-7
5.43*
10
-7
0.43 *
10
-7
94%
92 %
0 FIT
234 FIT
543 FIT
43 FIT
T[PROOF] =
1 year
2 years
5 years
PFD
avg =
2.88 * 10
-4
4.67 * 10
-4
1.01 * 10
-3



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com