Back Button K6CM-VB Datasheet HTML 17Page - Omron Electronics LLC K6CM-VB Datasheet HTML 18Page - Omron Electronics LLC K6CM-VB Datasheet HTML 19Page - Omron Electronics LLC K6CM-VB Datasheet HTML 20Page - Omron Electronics LLC K6CM-VB Datasheet HTML 21Page - Omron Electronics LLC K6CM-VB Datasheet HTML 22Page - Omron Electronics LLC K6CM-VB Datasheet HTML 23Page - Omron Electronics LLC K6CM-VB Datasheet HTML 24Page - Omron Electronics LLC K6CM-VB Datasheet HTML 25Page - Omron Electronics LLC Next Button
Zoom Inzoom in Zoom Outzoom out
 21 / 40 page
background image
K6CM-VB
21
Nomenclature
Note: Warning:
Indicates that it is time for maintenance.
Critical:
Indicates that it is time for replacement.
*1. Can be used only with EIP CPU version 1.2 or higher.
*2. Trigger modes other than external trigger
Always:
Trigger is not used. Measurement/monitoring are performed continuously after the power of the K6CM unit is turned on.
Internal trigger:
Measurement/monitoring starts based on the relation between the measured value and set value (trigger level).
You can use "Trigger Type" to specify whether measurement/monitoring start and continue for a set time when the measured
value is over, or under, the set value (trigger level), or are executed while the measured value exceeds the set value (trigger
level).
Also, the external trigger function can be used only when the insulation resistance type is EIP CPU version 1.1 or higher.
Name
Meaning
Alarm bar
A bar on which the color of the emitted
light changes according to the alarm
status.
It is indicated in the following colors during measurement/monitoring.
Green: Alarm status (normal)
Yellow: Alarm status (Warning)
Red: Alarm status (Critical)
The alarm bar is lit out in each of the following states:
When the power is OFF, when measurement is not being performed, and when a self-
diagnosis error has occurred, etc.
Measurement type
Indicates the type of the measured value
being displayed. The type can be
switched each time the [DISP] key is
pressed on the front operation part.
“G”: Acceleration, “mm/s”: Velocity, “T”; Motor temperature,
“
T”: Temperature Gap (difference between motor temperature and room
temperature)
Front
operation
part
[ALM RST] key
Releases the latched alarm state.
The main use of this key is to release the latched and fixed alarm state after returning
from the fault state to the normal state.
[DISP] key
Switches the type of the measured value being displayed.
You can switch between display-fixed mode and display auto switching mode by long-pressing for 3 seconds.
*1
Others
If two keys are simultaneously pressed and held for 5 seconds or longer, all settings of the main unit are reset to factory defaults.
Main unit status display
The status of the main unit is indicated by
lighting of the LCD characters.
“MON”: Measurement / monitoring is being performed
“ERR”: A self-diagnosis error has occurred
“AGE”: Running Time notification (it is recommended to replace the product main unit)
Transistor
output
13-14
Output of the alarm status (Warning).
Can be set to Normally Closed or
Normally Open.
When measurement/monitoring is in progress,
and the output method is Normally Closed
ON = Comprehensive alarm: Normal / OFF = Comprehensive alarm: Warning or Critical
and the output method is Normally Open
OFF = Comprehensive alarm: Normal / ON = Comprehensive alarm: Warning or Critical
15-16
Output of the alarm status (Critical).
Can be set to Normally Closed or
Normally Open.
When measurement/monitoring is in progress,
and the output method is Normally Closed
ON = Comprehensive alarm: Warning or Normal / OFF = Comprehensive alarm: Critical
and the output method is Normally Open
OFF = Comprehensive alarm: Warning or Normal / ON = Comprehensive alarm: Critical
17-18
Self-diagnosis error output.
OFF: A self-diagnosis error has occurred
ON: Other than the above
External
trigger input
3-4
Input of the external contact signal to
control measurement timing.
You can use "Trigger Type" to specify whether measurement/monitoring continue for a
set time after starting by the rise or fall of the external contact, or are executed while the
external contact is ON.
You can also specify settings to enable selection of a trigger mode other than external
trigger.
*2
· Unit power supply
· External trigger input
Push-in Plus terminal
2D code
· Sensor input
Push-in Plus terminal
· Transistor output
Push-in Plus terminal
[ALM RST] key
[DISP] key
Current value, minimum value,
and maximum measurement value type
Measurement value units
(measurement type)
Alarm bar
Main unit status display
Front operation part
EtherNet/IP port
Product status display
Network status display
LCD display for measured
values and other values
Hook



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com