Back Button EMC2103 Datasheet HTML 26Page - SMSC Corporation EMC2103 Datasheet HTML 27Page - SMSC Corporation EMC2103 Datasheet HTML 28Page - SMSC Corporation EMC2103 Datasheet HTML 29Page - SMSC Corporation EMC2103 Datasheet HTML 30Page - SMSC Corporation EMC2103 Datasheet HTML 31Page - SMSC Corporation EMC2103 Datasheet HTML 32Page - SMSC Corporation EMC2103 Datasheet HTML 33Page - SMSC Corporation EMC2103 Datasheet HTML 34Page - SMSC Corporation Next Button
Zoom Inzoom in Zoom Outzoom out
 30 / 84 page
background image
RPM-Based Fan Controller with HW Thermal Shutdown
Datasheet
Revision 0.85 (01-29-08)
30
SMSC EMC2103
DATASHEET
5.7
Spin Up Routine
The EMC2103 also contains programmable circuitry to control the spin up behavior of the fan driver
to ensure proper fan operation. The Spin Up Routine is initiated under the following conditions when
the Tach Period Measurement method of tach measurement is used. This applies to either the RPM
based Fan Speed Control Algorithm mode or the Direct Setting mode (with or without the Look Up
Table).
1. The TACH Target Register value changes from a value of FFh to a value that is less than the Valid
TACH Count (see Section 8.10 and Section 8.12).
2. The RPM based Fan Speed Control Algorithm’s measured TACH Reading Register value is greater
than the Valid TACH Count setting.
When the Spin Up Routine is operating, the fan driver is set to full scale (optional) for one quarter of
the total user defined spin up time. For the remaining spin up time, the fan driver output is set a a user
defined level (30% through 65% drive).
After the Spin Up Routine has finished, the EMC2103 measures the TACH signal. If the measured
TACH Reading Register value is higher than the Valid TACH Count Register setting, the FAN_SPIN
status bit is set and the Spin Up Routine will automatically attempt to restart the fan.
Figure 5.5 shows an example of the Spin Up Routine in response to a programmed fan speed change
based on the first condition above.
Figure 5.5 Spin Up Routine
100%
(optional)
30% through 65%
Algorithm controlled drive
Fan Step
Spin Up Time
¼ of Spin Up Time
Update Time
Target Count
Changed
Target Count
Reached
New Target Count
Prev Target
Count = FFh
Check TACH



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com