3 / 5 page ![]() Switching capacity AC Rated making capacity cos = 0.35 A 950 Rated breaking capacity, motor load switch cos = 0.35 230 V A 760 400 V A 740 500 V A 880 690 V A 520 Rated operational current 440 V load−break switch AC−21A Ie A 100 AC−3 motor load switch motor rating 230 V P kW 22 400 V P kW 37 500 V P kW 45 690 V P kW 37 AC−23A Motor load switches (main switches maintenance switches) 230 V P kW 30 400 V P kW 50 500 V P kW 65 690 V P kW 45 DC DC−1, Load−break switches L/R = 1 ms Rated operational current Ie A 100 Voltage per contact pair in series V 60 DC−23A, Motor load switches L/R = 15 ms 24 V Rated operational current Ie A 50 Contacts Quantity 1 48 V Rated operational current Ie A 50 Contacts Quantity 2 60 V Rated operational current Ie A 50 Contacts Quantity 3 3 |
|
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|