LBTV
1of 2
H52424
01/02
(800) 545-6258
www.tycothermal.com
Tyco Thermal Controls
Electrical freeze protection for long
pipelines in both nonhazardous and
hazardous (classified) locations
The LBTV self-regulating heating cables pro-
vide freeze protection and low-temperature
maintenance for longline applications. The
LBTV heating cables maintain process
temperatures up to 150°F (65°C) and can
withstand intermittent exposure to tempera-
tures up to 185°F (85°C).
The cables are configured for use in nonhaz-
ardous and hazardous (classified) locations,
including areas where corrosives may be
present.
The LBTV heating cables provide long circuit
length capability. They can be used for con-
tinuous circuit lengths up to 1125 feet
powered from a single source. LBTV cables
are especially well suited for tracing long
pipelines containing temperature-sensitive
fluids or where high reliability is required.
Raychem® LBTV cables meet the require-
ments of the U.S. National Electrical Code
and the Canadian Electrical Code. For addi-
tional information, contact your Tyco
Thermal Controls representative or call Tyco
Thermal Controls at (800) 545-6258.
Nickel-plated copper bus wire (10 AWG)
Self-regulating conductive core
Modified polyolefin inner jacket
Tinned-copper braid
Fluoropolymer outer jacket (-CT)
Self-regulating heating cables
Application
Area classification
Nonhazardous and hazardous (classified) locations
Traced surface type
Metal and plastics
Chemical resistance
Organic and aqueous inorganic chemicals and corrosives
Supply voltage
200–277 Vac
Temperature rating
Maximum maintain or continuous
150°F (65°C)
exposure temperature (power on)
Maximum intermittent exposure
185°F (85°C)
temperature, 1000 hours (power on or off)
Temperature ID number (T-rating)
T6, 185°F (85°C)
Temperature ID numbers are consistent with North America national electrical codes.
Approvals
Hazardous Locations
Zone Approvals
Design and installation
For proper design and installation, use TraceCalc® Pro software or the Design section of the
Industrial Product Selection and Design Guide. Literature is available through the Tyco Thermal
Controls Fax-on-Demand system and via the Tyco Thermal Controls Web site,
www.tycothermal.com.
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups F, G
Class III
Class I, Div. 1 and 2, Groups A, B, C, D
Class II, Div. 1 and 2, Groups E, F, G
Class III
Class I, Div. 2, Groups A, B, C, D
Class II, Div. 2, Groups F, G
Heating cable construction
CLI, ZN1, AEx e II
R