Z204687-0D
PAGE 4
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
03131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
AA01
INSTALLATION GUIDE
FOR CDE DEVICE WITH PEAR-SHAPED
SENSOR
1. Remove the cover and connect the gas cylinder hose to the plastic port located on
the sensing module. Connect only one sensor to the calibration gas cylinder at a
time.
Connect hose here
2. Start flowing nitrogen gas (0 ppm CO
2). Use a flow rate of 0.3 to 0.5 liter/minute.
NITROGEN
GAS
Regulator
Valve
3. Push and hold down the calibration button until the LED illuminates.
Push and hold down calibration button
Green LED
4. Continue flowing gas through the sensor until the LED deluminates. Estimated
calibration time is 5 minutes. Remove the hose from the calibration port when
complete.
FOR CWE DEVICE WITH PEAR-SHAPED
SENSOR
1. Remove the cover and connect the gas cylinder hose to the plastic port located on
the sensing module. Connect only one sensor to the calibration gas cylinder at a
time.
Connect hose here
2. Start flowing nitrogen gas (0 ppm CO
2). Use a flow rate of 0.3 to 0.5 liter/minute.
NITROGEN
GAS
Regulator
Valve
3. Push and hold down the calibration button until the LED illuminates.
Push and hold down calibration button
Green LED
4. Continue flowing gas through the sensor until the LED deluminates. Estimated
calibration time is 5 minutes. Remove the hose from the calibration port when
complete.



Html Pages

1 2 3 4


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com