Walk Test SpectrAler t horn/strobe and horn only
work on “walk tests” with time durations of
4 seconds or greater
Input Terminals
12 to 18 AWG
Dimensions
Strobe and horn/strobe with universal plate
5
″ x 55/8″ x 2 15/16″
Strobe and horn/strobe with small
footprint plate
3 3/8
″ x 55/8″ x 2 5/16″
Horn with universal mounting plate
5
″ x 55/8″ x 1 5/16″
Horn without mounting plate
2 15/16
″ x 55/16″ x 1 5/16″
Weight, horn only
7.2 oz.
Weight, strobe and horn/strobe
8.8 oz.
Mounting
4
″ x 4″ x 11/2″ or 2″ x 4″ x 17/8″
standard boxes
Indoor Operating Temperature
32°F to 120°F (0°C to 49°C)
Maximum humidity
95% as tested per UL464
Weatherproof (horn and horn/strobes)
Operating Temperature
32°F to 150°F (0°C to 66°C)
(outdoor strobe only)
–40°F to 158°F (–40°C to 70°C)
ULC Canadian Models
–40°C to 66°C
Voltages
12 or 24VDC and FWR unfiltered
Operating voltage range*
12V: 10.5-17V; 24V: 20-30V
Operating voltage range*
(with Sync•Circuit module, MDL)
12V, 11-17V; 24V, 20-30V
* These products should be operated within their rated
voltage range; UL does, however, test functional
integrity to -20% and +10% of manufacturer's stated
ranges.
U.S. Patent Numbers
5,593,569
5,914,665
6,049,446
Specifications
Engineering Specifications
General
SpectrAlert horns, strobes and horn/strobes shall be capa-
ble of mounting to a standard 4
″ x 4″x 11/2″ back box or a
single gang 2
″ x 4″ x 17/8″ back box using the universal
mounting plate included with each SpectrAlert product.
Also, SpectrAlert products, when used in conjuction
with the accessory Sync•Circuit Module, shall be pow-
ered from a non-coded power supply and shall operate
on 12 or 24 volts. 12 volt rated devices shall have an
operating voltage range of 10.7–17 volts. 24-volt rated
devices shall have an operating voltage range or 20–30
volts. SpectrAlert products shall have an operating tem-
perature of 32° to 120°F and operate from a regulated
DC or full wave rectified, unfiltered power supply.
Horn
Horn shall be a System Sensor SpectrAlert Model
capable of operating at 12 and 24 volts. Horn shall be
listed to UL 464 for fire protective signaling systems. The
horn shall have two tone options, two audibility options
(at 24 volts) and the option to switch between a temporal
3 pattern and a non-temporal continuous pattern. All horn
models shall operate on a coded power supply.
Strobe
Strobe shall be a System Sensor SpectrAlert Model
listed to UL 1971 and be approved for fire protective
service. The strobe shall be wired as a primary signaling
notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appli-
ances, flashing at 1Hz over the strobe’s entire operating
voltage range. The strobe light shall consist of a xenon
flash tube and associated lens/reflector system.
Horn/Strobe Combination
Horn/Strobe shall be a System Sensor SpectrAlert Model
listed to UL 1971 and UL 464 and shall be
approved for fire protective service. Horn/strobe shall
be wired as a primary signaling notification appliance
and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at
1Hz over the strobe’s entire operating voltage range.
The strobe light shall consist of a xenon flash tube and
associated lens/reflector system. The horn shall have two
tone options, two audibility options (at 24 volts) and the
option to switch between a temporal 3 pattern and a
non-temporal continuous pattern. Strobes shall be powered
independently of the sounder with the removal of factory
installed jumper wires. The horn on horn/strobe models
shall operate on a coded or non-coded power supply
(the strobe must be powered continuously).
Synchronization Module
Module shall be a System Sensor Sync•Circuit
listed to UL 464 and shall be approved for fire protective
service. The module shall synchronize SpectrAlert strobes
at 1Hz and horns at temporal 3. Also, the module shall
silence the horns on horn/strobe models, while operating
the strobes, over a single pair of wires. The module shall
be capable of mounting to a 411/16
″ x 411/16″x 21/8″ back
box and shall control two Style Y (class B) or one Style Z
(class A) circuit. Module shall be capable of multiple zone
synchronization by daisy chaining multiple modules
together and re-synchronizing each other along the chain.
The module shall not operate on a coded power supply.



Html Pages

1 2 3 4


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com