3
/// /
60-JS6dt3
//
Engine
Manufacturer
John Deere
Model
5030HF285
Type
4-Cycle
Arrangement
5-Inline
Displacement: Cu In (lit)
186 (3.05)
Bore: in (cm)
3.4 (8.6)
Stroke: in (cm)
4.1 (10.5)
Compression Ratio
18.2:1
Rated RPM
1,800
Engine Governor
JDEC
Max Power: Standby: bhp (kWm)
96 (72)
Regulation
±.25%
Frequency
60 Hz
Air Cleaner
Dry
//
Liquid Capacity (Lubrication)
Total Oil System: gal (lit)
2.96 (11.2)
Engine Jacket Water Capacity: gal (lit)
0.78 (2.9)
System Coolant Capacity: gal (lit)
4.08 (15.4)
//
Electrical
Electric Volts DC
12
Cold Cranking Amps Under 0°F (-17.8°C)
750
//
Fuel System
Fuel Supply Connection Size
3/8” NPT
Fuel Return Connection Size
3/8” NPT
Maximum Fuel Lift: ft (m)
10 (3)
Recommended Fuel
Diesel #2
Total Fuel Flow: gal/hr (lit/hr)
21.7 (82)
//
Fuel Consumption
At 100% of Power Rating: gal/hr (lit/hr)
5 (18.9)
At 75% of Power Rating: gal/hr( lit/hr)
3.8 (14.4)
At 50% of Power Rating: gal/hr (lit/hr)
2.5 (9.5)
//
Cooling - radiator System
Ambient Capacity of Radiator: °F (°C)
122 (50)
Max. Restriction of Cooling Air, Intake,
and Discharge Side of Rad.: in. H
20 (kPa)
0.5 (0.12)
Water Pump Capacity: gpm (lit/min)
26 (100)
Heat Rejection to Coolant: BTUM (kW)
2,590 (45.5)
Heat Rejection to Air to Air: BTUM (kW)
723 (12.7)
Heat Radiated to Ambient: BTUM (kW)
554 (10)
//
Air requirements
Aspirating: *SCFM (m3/min)
186 (5.3)
Air Flow Required for Rad.
Cooled Unit: *SCFM (m3/min)
5,765 (163)
Air Flow Required for Heat
Exchanger/Remote Rad. based
on 25°F Rise: *SCFM (m3/min)
1,250 (36)
* Air density = 0.0739 lbm/ft3 (1.184 kg/m3)
//
Exhaust System
Gas Temp. (Stack): °F (°C)
972 (522)
Gas Volume at Stack
Temp: CFM (m3/min)
484 (13.7)
Maximum Allowable
Back Pressure: in. H
20 (kPa)
30 (7.5)
Minimum Allowable
Back Pressure: in. H
20 (kPa)
16 (4)
aPPlication Data



Html Pages

1 2 3 4


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com