Technical data
Ambient conditions
Ambient temperature (storage/transport)
-40 °C ... 70 °C
Permissible humidity (operation)
5 % ... 85 %
Altitude
≤ 4000 m (amsl (above mean sea level))
Degree of protection
IP20
General
Housing material
Zinc die-cast
Color
silver/black
Mounting type
Connection-specific attachment plug and DIN rail, 35 mm
Type
Attachment plug for DIN rail mounting
Number of positions
8
Direction of action
Line-Line & Line-Ground/Shield
Protective circuit
IEC test classification
B2
C1
C2
C3
D1
Maximum continuous voltage UC (wire-wire)
≤ 3.3 V DC (±60 V DC/PoE)
Rated current
≤ 1.5 A (25 °C)
Operating effective current IC at UC
≤ 1 µA
Residual current IPE
≤ 400 µA
Nominal discharge current In (8/20) µs (line-line)
100 A
Nominal discharge current In (8/20) µs (line-earth)
2 kA (per signal pair)
Total discharge current Itotal (8/20) µs
10 kA
Nominal pulse current Ian (10/700) µs (line-line)
≤ 40 A
Nominal pulse current Ian (10/700) µs (line-earth)
≤ 160 A
Output voltage limitation at 1 kV/µs (line-line) spike
≤ 85 V (PoE)
Output voltage limitation at 1 kV/µs (line-earth) spike
≤ 700 V
Output voltage limitation at 1 kV/µs (line-line) static
≤ 9 V
Output voltage limitation at 1 kV/µs (line-earth) static
≤ 700 V
Residual voltage at In (line-line)
≤ 15 V
≤ 100 V (PoE)
Voltage protection level Up (line-line)
≤ 9 V (B2 - 1 kV / 25 A)
≤ 100 V (B2 - 1 kV / 25 A - PoE)
≤ 12 V (C3 - 20 A)
Voltage protection level Up (line-earth)
≤ 900 V (B2 - 4 kV / 100 A)



Html Pages

1 2 3 4 5 6


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com