Back Button ASC7511 Datasheet HTML 5Page - List of Unclassifed Manufacturers ASC7511 Datasheet HTML 6Page - List of Unclassifed Manufacturers ASC7511 Datasheet HTML 7Page - List of Unclassifed Manufacturers ASC7511 Datasheet HTML 8Page - List of Unclassifed Manufacturers ASC7511 Datasheet HTML 9Page - List of Unclassifed Manufacturers ASC7511 Datasheet HTML 10Page - List of Unclassifed Manufacturers ASC7511 Datasheet HTML 11Page - List of Unclassifed Manufacturers ASC7511 Datasheet HTML 12Page - List of Unclassifed Manufacturers ASC7511 Datasheet HTML 13Page - List of Unclassifed Manufacturers Next Button
Zoom Inzoom in Zoom Outzoom out
 9 / 19 page
background image
- 9 -
© Andigilog, Inc. 2006
www.andigilog.com
August 2006 - 70A04010
aSC7511
next one-shot reading or full activation. Standby mode is
discussed further in the Operation section.
THERM Limit Registers
There are two limit registers for the THERM function:
• THERM Remote High Limit
• THERM Local High Limit
These registers may be written or read-back at any time at
the addresses in shown in Table 2. Both limits has a default
value at power-up of 85°C.
The THERM alarm will be set when this limit is exceeded
and will reset when the temperature falls below that limit.
However, there is also a THERM hysteresis register that
may be used to set the temperature difference below
the THERM limit setting where the THERM alarm will be
reset once it has been triggered. This value is defaulted to
10°C and may be set to any value after power-on.
Operation of these registers in thermal management
applications is described in the Applications Section.
Remote Sensor Offset Register
Offset errors may be encountered on the remote sensor
readings caused by factors such as system clock noise
induced into the sensor interconnect or by a difference
between the measured temperature and the actual
temperature of interest in the system. A correction offset
value may be provided by the user to add or subtract from
the measured value resulting in a corrected value being
stored in the remote temperature registers. The limit values
will then be compared to these corrected values.
The offset register coding is two’s complement and it is
allocated two bytes at addresses 11h and 12h. Table 7
describes some examples of values in the range from -
128°C to +127.75°C that may be applied.
Offset Value
Offset Register
High Byte (11h)
Offset Register
Low Byte (11h)
+127.75°C
0111 1111
11 00 0000
+4°C
0000 0100
00 00 0000
+1°C
0000 0001
00 00 0000
+0.5°C
0000 0000
10 00 0000
0°C
0000 0000
00 00 0000
-0.5°C
1111 1111
10 00 0000
-1°C
1111 1111
00 00 0000
-4°C
1111 1100
00 00 0000
-128°C
1000 0000
00 00 0000
Table 7. Offset Register Sample Codes
Consecutive ALERT Register
This register will set the number of out of limit value
readings it will require before ALERT is asserted. It is
stored at register address 22h. The default value is for a
single out of limit reading to assert ALERT . The register
values for up to 4 out-of-limit readings are found in Table 8.
Number of Out-of-Limit
Measurements Required
Register Value
1
yxxx 000x
2
yxxx 001x
3
yxxx 011x
4
yxxx 111x
x = Don’t Care
y = SMBus Timeout Enable
Table 8. Consecutive Alert Register
This register is also used to control activation of the SMBus
timeout feature. It is disabled by default and enabled by
writing a 1 to the MSB, bit 7.
Manufacturer’s Registers
Manufacturer’s identification is stored in the register at
address FEh and set to the value 61h. Register FFh
contains the die revision code.
Serial Data Bus Operation
General Operation
Writing to and reading from the aSC7511 registers is
accomplished via the SMBus-compatible two-wire serial
interface. SMBus protocol requires that one device on the
bus initiate and control all read and write operations. This
device is called the “master” device. The master device
also generates the SCL signal that is the clock signal for all
other devices on the bus. All other devices on the bus are
called “slave” devices. The aSC7511 is a slave device.
Both the master and slave devices can send and receive
data on the bus.
During SMBus operations, one data bit is transmitted per
clock cycle. All SMBus operations follow a repeating nine
clock-cycle pattern that consists of eight bits (one byte) of
transmitted data followed by an acknowledge (ACK) or not
acknowledge (NACK) from the receiving device. Note that
there are no unused clock cycles during any operation—
therefore there must be no breaks in the stream of data
and ACKs / NACKs during data transfers.
For most operations, SMBus protocol requires the SDA line
to remain stable (unmoving) whenever SCL is high — i.e.



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com