Mounting Base Selection Guide
Base Model
Loop
Current
Alarm
Nominal
Current Draw
Number
Version
Type
Limit Resistor
Contact Type
Voltage
on Alarm (mA)
B401B
UL/ULC
2-wire*
No
—
12/24VDC††
10–100**
B401BR
UL/ULC
2-wire*
Yes
—
24VDC
10–62
B402B
UL/ULC
4-wire
Yes
Form A&C
24VDC
14–39
B404B
UL/ULC
4-wire
Yes
Form A&C+A
120VAC
75 mA AC Max
Supervisory
B406B
UL/ULC/EN-54 2-wire*
No
Form C
24VDC
12–100**
B401†
UL/EN-54
2-wire*
No
—
12/24VDC††
10–100**
B401R†
EN-54
2-wire*
Yes
—
24VDC
10–62
*Functionality contingent on panel compatibility.
**Must be limited by control panel.
Operating Voltage/Alarm Current:
Mounting base dependent (see chart
on page 2)
Standby Current:
Ion:
120 µA maximum
Thermal:
100 µA maximum
Sensitivity:
1.9% + ±6%/ft. Ion
Weight:
1451:
0.5 lb. (227 gm)
5451:
0.3 lb. (136 gm)
Size:
3.2”/8.1 cm height
4.0”/10.2 cm diameter,
unflanged base
6.2”/15.7 cm diameter,
flanged base
Construction:
Flame retardant Noryl plastic
Operating Temperature:
1451:
32°F to 120°F (0°C to 49°C)
5451:
32°F to 100°F (0°C to 38°C)
Alarm Point, Thermal:
135°F (57.2°C) or 15°F/min.
rate of rise
Humidity Range:
10 – 93% RH non-condensing
Air Velocity Rating:
Ionization: 1200 fpm maximum
Smoke Detector Spacing:
For ion detectors on smooth ceilings
(as defined in NFPA 72), spacing of
30 feet (900 sq. ft.) may be used
as a guide. For thermal detectors on
smooth ceilings (as defined in NFPA
72), spacing of 50 feet (2500 sq. ft.)
may be used. Other spacing may be
used depending on ceiling height, high
air movements, and other conditions
or response requirements.
Specifications
Junction Box Selection Guide*
Single
Gang
3.5” Octagon
4” Octagon
4” Square
50 mm
60 mm
75 mm
B401/B401R
No
No
No
No
Yes
Yes
No
B401B/BR
Yes
Yes
Yes
Yes
No
No
No
B402B/B406B Yes
Yes
Yes
Yes
Yes
Yes
Yes
B404B
No
No
Yes
Yes
No
No
No
* Box depth contingent on base and wire size.
Refer to National Electrical Code of local applicable codes for appropriate recommendations.
Relay Contact Ratings:
Resistive or Inductive
(60% power factor) load.
Form A:
2.0A at 30 VAC/DC
Form C:
0.6A at 110VDC, 2.0A at 30VDC
1.0A at 125VAC, 2.0A at 30VAC
†Flangeless base
†† Although B401B and B401 bases are capable
of operating at 12 and 24 VDC, they cannot be
used with the 5451 in 12 V applications.



Html Pages

1 2 3 4


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com