  38N Datasheet HTML 1Page - M-System Co.,Ltd. 38N Datasheet HTML 2Page - M-System Co.,Ltd. 38N Datasheet HTML 3Page - M-System Co.,Ltd. 38N Datasheet HTML 4Page - M-System Co.,Ltd. 38N Datasheet HTML 5Page - M-System Co.,Ltd. 38N Datasheet HTML 6Page - M-System Co.,Ltd. 38N Datasheet HTML 7Page - M-System Co.,Ltd. 38N Datasheet HTML 8Page - M-System Co.,Ltd. 38N Datasheet HTML 9Page - M-System Co.,Ltd. Next Button
Zoom Inzoom in Zoom Outzoom out
 3 / 10 page
background image
ES-4561 Rev.4
P. 3 / 10
MODEL & SUFFIX CODE SELECTION
38N–2
MODEL
INPUT
Dry contact or open collector
OUTPUT
Voltage or dry contact (jumper selectable)
FUNCTION
2 :Test circuit
ORDERING INFORMATION
Specify code number. (e.g. 38N-2)
GENERAL SPECIFICATIONS
Construction: rack mounted; terminal access via
screw terminals at the front and via
connector at the rear
Connection
Input:
M3.5 screw terminals
DCS I/O: card-edge connector
Output: M3.5 screw terminals
Power input: supplied from card-edge connector
Screw terminal material: nickel-plated steel
(torque 0.8 N·m)
Fuse:
0.5A
Alarm contact: dry contact output at the screw
terminal when the fuse is blown
Isolation:
input or power to output
Test switch: LED provided
INPUT
■CONTACT INPUT: dry contact or open collector
Contact detecting: 24V DC, approx. 20mA
■DCS STATUS OUTPUT: dry contact or open collector
Contact detecting: 24V DC, approx. 20mA
OUTPUT
■ELECTROMAGNETIC VALVE: voltage contact
Rated load: 120V AC @0.5A (cosø=1)
24V DC @0.5A (resistive load)
Load current: 8A max. for the total of 16 channels
■DRY CONTACT: dry contact (electromagnetic valve
or dry contact selectable with the jumper
on the PCB)
Rated load: 120V AC @3A (cosø=1)
24V DC @3A (resistive load)
Relay protection: For maximum relay life with
inductive loads (e.g. coil), external
protection including noise quenching is
recommended.
■DCS STATUS INPUT: relay contact
Rated load: 30V DC @3A (resistive load)
INSTALLATION
Power input: 24V DC ±10%, approx. 35mA
(ripple 10% p-p max.)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90% RH (non-condensing)
Mounting: Standard Rack 38N-B❑
Dimensions: W23×H149×D102 mm
(0.91"×5.87"×4.02")
Weight:
150 g (0.33 lbs)
PERFORMANCE
Insulation resistance: ≥100MΩ with 500V DC
Dielectric strength: 1000V AC @1 minute
Relay life: mechanical life 5 × 107 cycles
electrical life 105 cycles
(30 cycles/min. at rated load)
FRONT VIEW mm (inch)
< LOOPBACK I/O RELAY CARD >
12
3 4
SW1
LED
SW2
FUSE
4–M3.5 SCREWS
23 (.91)
DISCONTINUED MODEL
Replaced with Model 38N2-2



Html Pages

1 2 3 4 5 6 7 8 9 10


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com