  B84299G Datasheet HTML 1Page - EPCOS B84299G Datasheet HTML 2Page - EPCOS B84299G Datasheet HTML 3Page - EPCOS B84299G Datasheet HTML 4Page - EPCOS B84299G Datasheet HTML 5Page - EPCOS B84299G Datasheet HTML 6Page - EPCOS B84299G Datasheet HTML 7Page - EPCOS B84299G Datasheet HTML 8Page - EPCOS B84299G Datasheet HTML 9Page - EPCOS  
Zoom Inzoom in Zoom Outzoom out
 3 / 9 page
background image
Capacitor configuration
The capacitors are able to handle peak current far in excess of the rms current. In this way they
can discharge high-energy transients without suffering damage.
The capacitors are self-healing and come with integrated overpressure disconnection. Con-
sequently a capacitor will not burst under inadmissible overload or at the end of its service life.
RF-tight cable routing from top cabinet area to shielding wall
RF-tight cable routing uses flexible connector fittings with an inner diameter of 80 mm. The con-
nector fittings must be ordered separately.
There are matching openings for the connector fittings on the rear of the cabinet. Unused open-
ings can be sealed with special cover flange plates.
Refer to the chapter on installation accessories for connector fittings and cover flange plates.
Installation
On the front and rear of its base, the filter cabinet has a plate that can be unscrewed. After re-
moving these plates, a cabinet can be simply moved with a forklift truck for example. There is a
ring at each corner on the top for use of a crane.
For enhanced protection against shock, there are openings in the bottom so that the cabinet can
be bolted to the floor.
Protective measures (grounding)
The high capacitances between the lines and ground require special protective measures. If there
are no product-specific requirements, protection with a secondary ground wire (cross section min.
10 mm2) in accordance with EN 50178 is necessary. For this purpose the filter case have con-
necting bolts at each end.
Resistors are incorporated in the filter to discharge capacitors after turn-off.
EMP protection
For overvoltage protection, the cabinet can be fitted with block varistors (model SIOV B80K…).
The advantage of varistors is the absence of follow-up current once the overvoltage has decayed.
These block varistors are also notable for their high discharge capacity (max. 100000 A for an
8/20 µs curve per line).
Filters for power lines
B84299G
Filter cabinets (300 to 1600 A)
3



Html Pages

1 2 3 4 5 6 7 8 9


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com