Back Button 8553 Datasheet HTML 14Page - PHOENIX CONTACT 8553 Datasheet HTML 15Page - PHOENIX CONTACT 8553 Datasheet HTML 16Page - PHOENIX CONTACT 8553 Datasheet HTML 17Page - PHOENIX CONTACT 8553 Datasheet HTML 18Page - PHOENIX CONTACT 8553 Datasheet HTML 19Page - PHOENIX CONTACT 8553 Datasheet HTML 20Page - PHOENIX CONTACT 8553 Datasheet HTML 21Page - PHOENIX CONTACT 8553 Datasheet HTML 22Page - PHOENIX CONTACT  
Zoom Inzoom in Zoom Outzoom out
 18 / 22 page
background image
AXL E ETH DI8 DO4 2A M12 6P
8553_en_03
PHOENIX CONTACT
18
13.5
Modbus timeout monitoring (1280)
Modbus monitoring means setting or reading the timeout
value for the Modbus connection monitoring.
A timeout value of 0 ms deactivates monitoring.
Enter the time in milliseconds in the range from 200 ms to
65000 ms, converted to hexadecimal.
13.6
Timeout OUT process data monitoring (pro-
cess data watchdog) (2000)
Timeout OUT process data monitoring means setting or
reading the timeout value for the process data watchdog.
Enter the time in milliseconds in the range from 200 ms to
65000 ms, converted to hexadecimal.
A timeout value of 0 ms deactivates the watchdog.
13.7
Fault response mode (2002)
The required fault response mode can be set via web-based
management or by writing to Modbus register 2002.
13.8
Net Fail reason (2002)
The reasons for a Fault Response and a set Net Fail signal
can be accessed via web-based management or via the
Modbus register 2004.
13.9
Command register (2006)
Only set one bit for the command register, otherwise an error
message is output. Only write access is enabled for the reg-
ister.
Connection monitoring with the new timeout
values is only activated after a Modbus/TCP
function has been executed on the relevant
TCP connection.
Code
(bin)
Code
(hex)
Meaning
00
0000
All outputs are set to “0”.
01
0001
All outputs are set to “1”.
10
0002
All outputs keep their last value.
Code (hex)
Meaning
0001 ... 0006 Reserved
0007
DTI timeout occurred
0008
Host timeout occurred
0009
Set by user.
000A
Connection aborted
000B
Initialization error
000C
Process data watchdog triggered
000D
Modbus timeout occurred
Bit
Code
(hex)
Meaning
00001
Reserved
10002
Reserved
20004
Reserved
30008
Reserved
40010
Set Net Fail
50020
Acknowledge Net Fail
60040
Reserved
7
0080
Delete a detected I/O warning/malfunction
80100
Reserved
90200
Reserved
10
0400
Reserved
11
0800
Reserved
12
1000
Reserved
13
2000
Reserved
14
4000
Reserved
15
8000
Reserved



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com