  FNP600 Datasheet HTML 1Page - Bel Fuse Inc. FNP600 Datasheet HTML 2Page - Bel Fuse Inc. FNP600 Datasheet HTML 3Page - Bel Fuse Inc. FNP600 Datasheet HTML 4Page - Bel Fuse Inc. FNP600 Datasheet HTML 5Page - Bel Fuse Inc. FNP600 Datasheet HTML 6Page - Bel Fuse Inc. FNP600 Datasheet HTML 7Page - Bel Fuse Inc. FNP600 Datasheet HTML 8Page - Bel Fuse Inc. FNP600 Datasheet HTML 9Page - Bel Fuse Inc. Next Button
Zoom Inzoom in Zoom Outzoom out
 2 / 12 page
background image
FNP600/850/1000
© 2015 Bel Power Solutions, Inc.
866.513.2839
tech.support@psbel.com
BCD20034-G_AE
MODEL
NOMINAL
OUTPUT
VOLTAGE
(VDC) 1
ADJUSTMENT
RANGE
(VDC)
MAXIMUM
OUTPUT
CURRENT
(Amps)
LINE
REGULATION
(%)
LOAD
REGULATION
(%) 2
RIPPLE &
NOISE
pk-pk % 3
COMPATIBLE
SHELF
FNP600-12
12
12 (Standby)
7 to 12
N/A
51
0.5
0.17
8
6
8
1
1
FNR-5-12
FNP850-12
12
12 (Standby)
7 to 12
N/A
73
0.5
0.17
8
6
8
1
1
FNR-5-12
FNP850-12R 4
12
12 (Standby)
7 to 12
N/A
73
0.5
0.17
8
6
8
1
1
FNR-5-12
FNP600-48
48
12 (Standby)
44 to 50.5
N/A
12.6
0.5
0.17
8
6
8
1
1
FNR-5-48
FNP1000-48
48
12 (Standby)
44 to 50.5
N/A
21
0.5
0.17
8
6
8
1
1
FNR-5-48
1 Models with 5V and 3.3V standby voltages are also available. (Contact factory.)
2 Primary 12V and 48V outputs have built-in droop regulation.
3 Maximum peak-to-peak noise expressed as a percentage of output voltage; 20 MHz bandwidth.
4 FNP850-12R model has airflow from rear to front.
Options
Suffixes to Add to Part Number
RoHS lead solder exemption
No RoHS suffix character required.
RoHS compliant for all 6 substances
Add "G" as the last character of the part number.
PARAMETER
CONDITIONS/DESCRIPTION
MIN.
NOM.
MAX.
UNITS
AC Input Voltage
Single-phase continuous input range.
90
264
VAC
Input Frequency
AC input.
47
63
Hz
Hold-up Time
After last AC line peak at full power.
At 115 VAC
201
ms
Input Current
At full-rated load.
At 90 VAC
14
A rms
Inrush Surge Current
Internally limited. Vin = 230 VAC, T = 25 ºC
34
A pk
Power Factor
Per EN61000-3-2
0.97
W/VA
1 FNP1000-48 model has a hold-up time of 16 ms
PARAMETER
CONDITIONS/DESCRIPTION
MIN.
NOM.
MAX.
UNITS
Efficiency:
Full rated load at 230 VAC input.
FNP600-48
FNP1000-48
FNP600-12
FNP850-12
88
88
84
84
89.5
89.5
87
87
%
Minimum Load
Minimum loading required to maintain regulation.
0
A
Output Power
FNP1000
FNP850
FNP600
1006
856
600
W
Overshoot
Output voltage overshoot at turn-on.
3
%
Transient Response
Maximum recovery time to within 1%
of initial set point due to a 50% load
change, 1A/µs.
12V or 48V output:
Standby output:
400
2
µs
ms
Maximum deviation:
12V or 48V output:
Standby output:
2
4
%
Turn-On Delay
Time required for initial output voltage stabilization after
application of AC input..
1.5
Sec
Output Regulation
See Model Selection table.



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com