| Electronic Components Datasheet Search |
|
AD9887APCB Datasheet(PDF) 39 Page - Analog Devices |
|
|
|||||||||||||||||||||||||||||
AD9887APCB Datasheet(HTML) 39 Page - Analog Devices |
|
39 / 44 page ![]() REV. 0 AD9887A –39– 1B 7-0 Test Register Must be set to 00H for proper operation. 1C 7-3 Test Bits Must be set to 0000 0 *** for proper operation. 1C 2 CbCr Output Order In 4:2:2 mode, the red and blue channels can be interchanged to help satisfy board layout or timing requirements, but the green channel must be configured for Y. 1C bit 2 controls the order that the U/V(CbCr) data is output. If this bit is high, the Red channel data precedes the Blue channel data. If this bit is low, the Blue channel data precedes the Red channel data. See the example in Table LI. Table LI. 4:2:2 Input/Output Configuration Input Channel Connection Output Format Red Y V/U if 1C bit 2 = 1, U/V if 1C bit 2 = 0 Green Y Y Blue U High Impedance 1C 1 Test Bits Must be set to 0 for standard input sampling. 1C 0 4:2:2 Output Mode Select 4:2:2 mode can be used to reduce the number of data lines used from 24 down to 16 for applications using YUV, YCbCr, or YPbPr graphics signals. A timing diagram for this mode is shown on page 22. Table LII. 4:2:2 Output Mode Select Select Output Mode 1 4:4:4 0 4:2:2 2-Wire Serial Control Port A 2-wire serial interface control port is provided. Up to four AD9887A devices may be connected to the 2-wire serial interface, with each device having a unique address. The 2-wire serial interface comprises a clock (SCL) and a bidirec- tional data (SDA) pin. The analog flat panel interface acts as a slave for receiving and transmitting data over the serial inter- face. When the serial interface is not active, the logic levels on SCL and SDA are pulled HIGH by external pull-up resistors. Data received or transmitted on the SDA line must be stable for the duration of the positive-going SCL pulse. Data on SDA must change only when SCL is LOW. If SDA changes state while SCL is HIGH, the serial interface interprets that action as a start or stop sequence. There are five components to serial bus operation: 1. Start signal 2. Slave address byte 3. Base register address byte 4. Data byte to read or write 5. Stop signal When the serial interface is inactive (SCL and SDA are HIGH), communications are initiated by sending a start signal. The start signal is a HIGH-to-LOW transition on SDA, while SCL is HIGH. This signal alerts all slaved devices that a data transfer sequence is coming. The first eight bits of data transferred after a start signal comprising of a 7-bit slave address (the first seven bits) and a single R/ W bit (the eighth bit). The R/ W bit indicates the direction of data trans- fer, read from (1) or write to (0) the slave device. If the transmitted slave address matches the address of the device (set by the state of the SA1-0 input pins in Table LIII), the AD9887A acknowledges by bringing SDA low on the ninth SCL pulse. If the addresses do not match, the AD9887A does not acknowledge. Table LIII. Serial Port Addresses Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 A6 A5 A4 A3 A2 A1 A0 (MSB) 10 01100 10 01101 10 01110 10 01111 Data Transfer via Serial Interface For each byte of data read or written, the MSB is the first bit of the sequence. If the AD9887A does not acknowledge the master device during a write sequence, the SDA remains HIGH so the master can generate a stop signal. If the master device does not acknowledge the AD9887A during a read sequence, the AD9887A interprets this as “end of data.” The SDA remains HIGH so the master can generate a stop signal. Writing data to specific control registers of the AD9887A requires that the 8-bit address of the control register of interest be written after the slave address has been established. This control register address is the base address for subsequent write operations. The base address autoincrements by one for each byte of data written after the data byte intended for the base address. If more bytes are transferred than there are available addresses, the address will not increment and will remain at its maximum value of 1Dh. Any base address higher than 1Dh will not produce an acknowledge signal. Data is read from the control registers of the AD9887A in a similar manner. Reading requires two data transfer operations. The base address must be written with the R/ W bit of the slave address byte LOW to set up a sequential read operation. Reading (the R/ W bit of the slave address byte HIGH) begins at the previously established base address. The address of the read register autoincrements after each byte is transferred. To terminate a read/write sequence to the AD9887A, a stop signal must be sent. A stop signal comprises a LOW-to-HIGH transition of SDA while SCL is HIGH. The timing for the read/write operations is shown in Figure 37; a typical byte transfer is shown in Figure 38. A repeated start signal occurs when the master device driving the serial interface generates a start signal without first generating a stop signal to terminate the current communication. This is used to change the mode of communication (read, write) between the slave and master without releasing the serial interface lines. |
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |