Back Button TP37 Datasheet HTML 132Page - Siemens Semiconductor Group TP37 Datasheet HTML 133Page - Siemens Semiconductor Group TP37 Datasheet HTML 134Page - Siemens Semiconductor Group TP37 Datasheet HTML 135Page - Siemens Semiconductor Group TP37 Datasheet HTML 136Page - Siemens Semiconductor Group TP37 Datasheet HTML 137Page - Siemens Semiconductor Group TP37 Datasheet HTML 138Page - Siemens Semiconductor Group TP37 Datasheet HTML 139Page - Siemens Semiconductor Group TP37 Datasheet HTML 140Page - Siemens Semiconductor Group Next Button
Zoom Inzoom in Zoom Outzoom out
 136 / 230 page
background image
12-8
TP27, TP37 Equipment Manual
Release 01/00
12.2.1
Power Supply and Relay Contacts
The power supply for the Touch Panel is connected at the 4–pin plug connector
on the underside of the unit . Use the 4–pin terminal block supplied with the
TP for this purpose. The terminal block is designed for cables with a
cross–section not larger than 2.5 mm2. Please refer to the technical data in
Appendix A of information on the power supply requirements.
When configured accordingly, messages on the Touch Panel can trigger visual
and acoustic signals (lights, flashing lights, buzzer, sirens etc.) by tripping an
internal relay. The relay contacts are also carried to the 4–pin plug connector.
The figure below illustrates assignment of the 4–pin plug connector for the
power supply and relay contacts.
12 3 4
Relay contacts (NO contacts)
Rating 24 V DC; 0.4 A
(no inductive load)
GND
+ 24 V DC
!
Caution
S With a 24 V supply, make sure that the extra–low voltage is isolated safely.
Use only power supply units complying with IEC 364-4-41 or
HD 384.04.41 (VDE 0100, Part 410).
S The supply voltage must be within the specified voltage range. Voltages
outside this range can cause malfunctions.
A sensor monitors the temperature on the inside of the TP37. The contacts of
the internal relay close if the temperature exceeds the permissible limit value.
The relay contacts are carried to a 2–pin plug connector. This connector can be
used to drive an external fan, for instance.
The figure below illustrates the assignment of the 2–pin plug connector.
12
Relay contacts (NO contacts)
Rating 24 V DC; 0.4 A
(no inductive load)
Connect the ground connection
of the unit to the cabinet ground. To do so,
use the grounding screwdriver supplied.
Power supply
Relay contacts
(TP27-6 and
TP37) only
Temperature
monitoring ( TP37
only)
Ground
connection
Installation



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100  ...More


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com