  FNP3000 Datasheet HTML 1Page - Bel Fuse Inc. FNP3000 Datasheet HTML 2Page - Bel Fuse Inc. FNP3000 Datasheet HTML 3Page - Bel Fuse Inc. FNP3000 Datasheet HTML 4Page - Bel Fuse Inc. FNP3000 Datasheet HTML 5Page - Bel Fuse Inc. FNP3000 Datasheet HTML 6Page - Bel Fuse Inc. FNP3000 Datasheet HTML 7Page - Bel Fuse Inc. FNP3000 Datasheet HTML 8Page - Bel Fuse Inc. FNP3000 Datasheet HTML 9Page - Bel Fuse Inc. Next Button
Zoom Inzoom in Zoom Outzoom out
 3 / 17 page
background image
FNP3000 Series
3
Asia-Pacific
+86 755 298 85888
Europe, Middle East
+353 61 225 977
North America
+1 408 785 5200
© 2018 Bel Power Solutions & Protection
BCD.00669_004
Stanby Output VSB
Output Voltage
3.3
VDC
Output Current
0
2
A
Ripple and Noise 1
33
mVp-p
Line and Load Regulation
±5%
Vset
Load Capacitance
1000
μF
Transient Response
50% step load, 1A/
μsec slew rate,
recovery to 1% within 1 msec
3
% Vset
Startup Time
5
sec
1 Measured at 20 MHz bandwidth at an oscilloscope jack on the output with 0.1
μF ceramic and 10 μF aluminum electrolyitc capacitors.
PARAMETER
CONDITIONS/DESCRIPTION
MIN
NOM
MAX
UNITS
Over Voltage Protection
V1: latch off
V2: latch off
110
60
120
Vdc
%
Over Current Protection
V1: constant current inception
V2: hiccup
62.5
2.6
A
A
Over Temperature Protection
at full load, auto recovery
55
°C
PARAMETER
DESCRIPTION / CONDITION
MIN
NOM
MAX
UNIT
Storage Temperature
Non-Condensing
-40
70
°C
Operating Temperature
@ full load no derating
0
50
Humidity
Storage
Operating Humidity
5
10
90
%
MTBF
Calculated per Telcordia SR-332 Issue 2, Sept 2006,
component stress method at Ta = 25°C
916
Khrs
Acoustic
ISO 7779-1999
60
dB LpAm
Cold 2
IEC 68 Part 2 – 1: at -10°C minimum for 4 hours
Dry Heat
IEC 68 Part 2 – 2: at 50°C minimum for 4 hours
Damp Heat, Cyclic
IEC 68 Part 2 – 30: at 20~45°C, 30~95 %RH
Low Air Pressure (operating)
IEC 68 Part 2 – 13: at 10,000 feet, 697 mbar
Vibration (Sinusoidal)
IEC 68 Part 2 – 6: at 10~58 Hz, 0.075 mm;
58~500 Hz, 10 m/s2, 1 octave/minute, 10 cycles/main axis
1
G
Shock
IEC 68 Part 2 – 27: at 300 m/s2, 11 ms, half sine wave 3
shocks / main axis
30
G
Bump
IEC 68 Part 2 – 29: at 150 m/s2, 6 ms, half sine wave 900
bumps / main axis
15
G
WEEE
Directive 2012/19/EU
RoHS
EU Directive 2011/65/EU
2 The module shall start up at -10°C, however it is not required that the full specification is achieved until the operational internal temperature has
risen to 0°C.



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com