| Electronic Components Datasheet Search |
|
TP37 Datasheet(PDF) 202 Page - Siemens Semiconductor Group |
|
|
|||||||||||||||||||||||||||||
TP37 Datasheet(HTML) 202 Page - Siemens Semiconductor Group |
|
202 / 230 page ![]() C-4 TP27, TP37 Equipment Manual Release 01/00 Remedy: Cause Message 200 Battery power no longer sufficient for internal data buffer on OP. Battery on memory is discharged, data may no longer be readable. Replace battery. Note: Replace the battery while the unit is switched on in order to prevent loss of data. 210 Internal error OP co-ordination area not receivable during startup. Press restart button. 212 Internal error Bit for changing operating mode has been inverted erro- neously. Restart OP. 213 Offline mode not possible at present. Try change of operating mode again later. 214 The job number sent by the PLC or configured in a func- tion field is too large. Check PLC program and configured screen. 217, 218 Overlapping specified/actual values. Check configuration of actual/specified values in the process link. 230 The minimum value is greater than the maximum value for variable limits. Correct the limit settings. 231 The minimum value is equal to the maximum value for variable scales. Correct the scale on the OP. 250 You can not switch to the desired operating mode. Check parameters of PLC job. 251 Error transferring data record to PLC. Check recipe configuration. 252 Function can not be executed as a function of the same group has not yet been completed (e.g.: setpoint entry is active, password list can not be opened). Wait until preceding function has been completed (or terminate function) and then invoke desired function again. 253 Access to data medium is not possible. 1. Floppy drive not present, 2. Floppy is read only, 3. Disk is not formatted. 254 The disk must be formatted before a data record can be saved for the first time. First format the disk. 255 Not enough space on disk for this data record. Delete data records that are no longer re- quired. 256 Not enough system memory available to execute the de- sired function. Try activating function again. Check con- figuration. 1. Move function to a different screen 2. Simplify screen structure 3. Do not use trends on screen in conjunc- tion with this function 257 Data record has been stored with a different version stamp than defined in the current configuration. If the data records are to continue to be used, the old version number must be en- tered in the recipe configuration. Caution: The structure of the recipe determines the assignment of data to a data record. 258 A parameter record has been selected as a recipe. Param- eter records can not be edited directly. Only individual data records of a parameter record can be edited. System Messages |
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |