16 / 20 page ![]() XT40.481, XT40.482 – X-Series 48V, 20A, THREE-PHASE INPUT Jan. 2007 / Rev. 1.0 DS-XT40.48x-EN All parameters are specified at 48V 20A, 3x400Vac (XT40.481) or 3x480Vac (XT40.482), 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany 16/20 26. APPLICATION NOTES 26.1. PERIODICAL PEAK POWER CAPABILITY Fig. 26-Periodical peak power compatibility. The short term power can be used periodically. The duration of the peak power (TP) must be shorter than 15s. The time between two peak power pulses must be three times longer than the duration of the preceding pulse length. t T 100% 125% POUT PNOM TP > 3x TP 26.2. CHARGING OF BATTERIES The power supply shall not be used to charge batteries. |
|
|
Link URL |
| Does ALLDATASHEET help your business so far? [ DONATE ] |
About Alldatasheet | Advertisement | Contact us | Privacy Policy | Link to Datasheet | Link Exchange | Manufacturer List All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|