Back Button LTC4261 Datasheet HTML 25Page - Analog Devices LTC4261 Datasheet HTML 26Page - Analog Devices LTC4261 Datasheet HTML 27Page - Analog Devices LTC4261 Datasheet HTML 28Page - Analog Devices LTC4261 Datasheet HTML 29Page - Analog Devices LTC4261 Datasheet HTML 30Page - Analog Devices LTC4261 Datasheet HTML 31Page - Analog Devices LTC4261 Datasheet HTML 32Page - Analog Devices LTC4261 Datasheet HTML 33Page - Analog Devices Next Button
Zoom Inzoom in Zoom Outzoom out
 29 / 82 page
background image
LTC4284
29
Rev. B
For more information www.analog.com
APPLICATIONS INFORMATION
LTC4284 monitors the integrity of the MOSFETs in two
ways, and acts on both of them in the same manner.
First, the LTC4284 monitors the MOSFET drain voltage
at the DRAIN pin. A comparator detects a DRAIN high
condition whenever DRAIN is above a reference volt-
age, VD,FET(TH) that can be configured to 72mV, 102mV,
143mV or 203mV (geometric scale) using the VDTH bits
in the CONFIG_2 register 0x0E.
Second, the LTC4284 monitors the GATE voltages. If the
MOSFETs are turned on, but the GATE1 and/or GATE2
voltages are lower than VIN – 1.8V, a GATE low condition
is detected. The logic that determines a GATE low condi-
tion depends on the operation mode (see Table 1). For
the parallel mode, in turn-on state, a GATE low condition
is detected in either of the following two conditions: (1)
both GATE1 and GATE2 are low; (2) One GATE is low but
not in current limit.
When either a DRAIN high or a GATE low condition is
present when the MOSFETs are commanded on, the
FET_BAD_STATUS bit in FAULT_STATUS register 0x03
is set and an internal FET bad fault timer is started. The
FTBD_DL bits in CONFIG_2 register 0x0E configures the
timer duration to 256ms, 512ms, 1.02s and 2.05s. If the
DRAIN voltage falls below VD,FET(TH) and the GATE low
conditions are cleared before the timer times out, the
FET_BAD_STATUS bit is cleared and the timer is reset.
If the timer does time out, the FET_BAD_FAULT bit in
FAULT register 0x04 is set and the MOSFETs are turned
off if the FET_BAD_TURN_OFF bit in CONTROL_1 reg-
ister 0x0A has been set. The DRAIN high condition also
activates TMR pull-up current when not in current limit
(see SOA Timer).
Note that during startup while the load is being charged,
the FET_BAD_STATUS bit is set and the FET bad fault
timer is running. To avoid undesired turn-off, the timer
duration must be configured long enough for the load to
be fully charged.
After the MOSFETs are turned off following a FET bad
fault, the FET_BAD_STATUS bit is cleared. The MOSFETs
are allowed to turn on again after a cooling delay if the
FET_BAD_RETRY bits in CONTROL_2 register 0x0B have
not been cleared. The cooling delay is the same as that
for an overcurrent fault and is configurable from 512ms
to 65.5s in binary scale using the COOLING_DL bits in
CONFIG_2 register 0x0E (see Table 11). During the cool-
ing delay the DELAY_STATUS bit in REBOOT register
0xA2 is set. It will be cleared when the delay expires. The
FET_BAD_RETRY bits configures the number of retries
following a FET bad fault to 1, 7 or infinity (see Table 10).
If a finite retry number is selected, a retry counter reset
timer of 16.4s is started upon the retry following a FET
bad fault. If the next FET bad fault occurs before the timer
expires, the retry counter increments and the timer is
reset. Otherwise the retry counter is reset. The retry coun-
ter and the counter reset timer for the FET bad fault are
independent of those for the overcurrent fault.
If the FET_BAD_RETRY bits in CONTROL_2 register 0x0B
have been cleared, the MOSFETs will remain off until the
FET_BAD_FAULT bit is reset (see Resetting Faults) or the
FET_BAD_TURN_OFF bit is cleared through I2C. In either
of those two cases, the MOSFETs are allowed to turn on
after the auto-retry delay expires.
Input Step and Optimum Output Ramp
In events such as battery hot swapping or supply surge,
the input voltage may experience a sudden step. The mag-
nitude of the input step, ∆V, can be as large as tens of
volts. As long as the input voltage does not exceed the
overvoltage limit, the input step is not a fault condition
and the system should stay on and operate through it.
In the presence of the load capacitor, the output does
not follow the input immediately, but rather ramps up
from the initial supply voltage to the new supply voltage
while charging the load capacitor. The VDS of the MOSFET
initially jumps to ∆V and then ramps down. Additionally,
during the output ramp the MOSFET not only carries the
load current, IL but also the capacitance charging cur-
rent, ICL, so the total power dissipation in the MOSFET
can be very large. If a large input step is possible, it is
usually the worst-case operating condition for the SOA
of the MOSFET, and proper MOSFETs must be selected
to withstand the stress.
In such a condition, the minimum temperature rise of the
MOSFET is achieved when ICL matches IL, or the total cur-
rent is twice the load current. In other words, the current



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com