Back Button PMP71 Datasheet HTML 106Page - Endress+Hauser Group Services AG PMP71 Datasheet HTML 107Page - Endress+Hauser Group Services AG PMP71 Datasheet HTML 108Page - Endress+Hauser Group Services AG PMP71 Datasheet HTML 109Page - Endress+Hauser Group Services AG PMP71 Datasheet HTML 110Page - Endress+Hauser Group Services AG PMP71 Datasheet HTML 111Page - Endress+Hauser Group Services AG PMP71 Datasheet HTML 112Page - Endress+Hauser Group Services AG PMP71 Datasheet HTML 113Page - Endress+Hauser Group Services AG PMP71 Datasheet HTML 114Page - Endress+Hauser Group Services AG Next Button
Zoom Inzoom in Zoom Outzoom out
 110 / 124 page
background image
Cerabar S PMC71, PMP71, PMP75
110
Endress+Hauser
Information on cleaning
• Endress+Hauser provides flushing rings as an accessory to enable cleaning of the process isolating
diaphragm without removing the transmitter from the process. For further information please
contact your local Endress+Hauser Sales Center.
• We recommend you perform CIP (cleaning in place (hot water)) before SIP (sterilization in place
(steam)) for pipe diaphragm seals. A frequent use of sterilization in place (SIP) will increase the
stress on the process isolating diaphragm. Under unfavorable circumstances in the long term view
we cannot exclude that a frequent temperature change could lead to a material fatigue of the
process isolating diaphragm and possibly to a leakage.
Installation instructions
Diaphragm seal systems
• The diaphragm seal together with the transmitter form a closed, calibrated system, which is filled
through ports in the diaphragm seal and in the measuring system of the transmitter. These ports
are sealed and must not be opened.
• For devices with a temperature isolator or capillary, a suitable fastening device (mounting bracket)
is recommended.
• When mounting, sufficient strain relief must be provided for the capillary line to prevent the
capillary from bending (capillary bending radius ≥ 100 mm (3.94 in)
• For more detailed installation instructions, Endress+Hauser provides its customers with the free
"Applicator Sizing Diaphragm Seal" tool, which is available on CD or can be downloaded online at
"www.endress.com/applicator".
Capillary
In order to obtain more precise measurement results and to avoid a defect in the device, mount the
capillaries as follows:
• vibration-free (in order to avoid additional pressure fluctuations)
• not in the vicinity of heating or cooling lines
• insulate if the ambient temperature is below or above the reference temperature
• with a bending radius ≥ 100 mm (3.94 in)
• When using diaphragm seal systems with a capillary, sufficient strain relief must be provided to
prevent the capillary from bending (capillary bending radius ≥ 100 mm (3.94 in)).
• In the case of devices with diaphragm seals and capillaries, the zero point shift caused by the
hydrostatic pressure of the filling liquid column in the capillaries must be taken into account when
selecting the measuring cell. If a measuring cell with a small measuring range is selected, a
position adjustment can cause range violation.
Heat insulation
The PMP75 must only be insulated up to a certain height. The maximum permitted insulation height
is indicated on the devices and applies to an insulation material with a heat conductivity ≤ 0.04
W/(m x K) and to the maximum permitted ambient and process temperature. The data were
determined under the most critical application "quiescent air". Maximum permitted insulation height,
here indicated on a PMP75 with a flange:
A
B
1
2
A0020474
A
Ambient temperature ≤ 70 °C (158 °F)
B
Process temperature 400 °C (752 °F), depends on the diaphragm seal filling oil used
1
Maximum insulation height
2
Insulation material



Html Pages

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100  ...More


Datasheet Download

Go To PDF Page


Link URL



Does ALLDATASHEET help your business so far?  [ DONATE ] 

About Alldatasheet   |   Advertisement   |   Contact us   |   Privacy Policy   |   Link to Datasheet    |   Link Exchange   |   Manufacturer List
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com